- 铝绞线全标准 - AAC Conductor |
●AAC Conductor All Aluminum Stranded Conductor Standard:BS 215 Part1 1970 |
Nominal cross section(mm2) |
Nos.of Stranding & Diameter(Nos./mm) |
Calculated Cross section area(mm2) |
Approx Overall Diameter(mm) |
Mass of Conductor(Kg/Km) |
Calculated min.Breaking Load(KN) |
Calculated D.C.Resistance at 20℃(Ohm/Km) |
Delivery length(Meter) |
Drum Designation |
22 |
7/2.06 |
23.33 |
6.18 |
63.88 |
407 |
1.2270 |
2500×2 |
PL1000 |
25 |
7/2.21 |
26.85 |
6.63 |
73.53 |
468 |
1.0660 |
2500×2 |
PL1000 |
35 |
7/2.59 |
36.88 |
7.77 |
101.00 |
614 |
0.7762 |
3200 |
PL1000 |
50 |
7/3.10 |
52.83 |
9.30 |
144.70 |
845 |
0.5419 |
2600 |
PL1000 |
60 |
7/3.40 |
63.55 |
10.20 |
174.00 |
1010 |
0.4505 |
2200 |
PL1000 |
70 |
7/3.78 |
78.54 |
11.34 |
215.10 |
1221 |
0.3645 |
2700 |
PL1120 |
100 |
7/4.39 |
106.00 |
13.17 |
290.20 |
1633 |
0.2707 |
2300 |
PL1250 |
150 |
19/3.25 |
157.60 |
16.25 |
433.60 |
2622 |
0.1825 |
2900 |
PL1500 |
200 |
19/3.78 |
213.20 |
18.90 |
586.60 |
3306 |
0.1349 |
2300 |
PL1600 |
250 |
19/4.22 |
265.70 |
21.10 |
731.27 |
4122 |
0.1083 |
2000 |
PL1600 |
300 |
19/4.65 |
322.70 |
23.25 |
877.70 |
4974 |
0.08916 |
3000 |
PL1800 |
350 |
37/3.58 |
327.60 |
25.06 |
1021.00 |
5846 |
0.07739 |
2700 |
PL1800 |
400 |
37/3.78 |
415.20 |
26.46 |
1145.00 |
6439 |
0.06944 |
2400 |
PL1800 |
450 |
37/4.09 |
486.20 |
28.63 |
1341.00 |
7533 |
0.05930 |
2000 |
PL1800 |
500 |
37/4.27 |
529.80 |
29.89 |
1461.00 |
8178 |
0.5442 |
2100 |
PL1800 |
600 |
37/4.65 |
628.30 |
32.55 |
1732.00 |
9685 |
0.04590 |
1600 |
PL2000 | |
●AAC Conductor All Aluminum Stranded Conductor Standard:DIN 48201 Blatt |
Nominal cross section(mm2) |
Nos.of Stranding & Diameter(Nos./mm) |
Calculated Cross section area(mm2) |
Approx Overall Diameter(mm) |
Calculated min.Breaking Load(KN) |
Mass of Conductor(Kg/Km) |
Calculated D.C.Resistance at 20℃(Ohm/Km) |
Delivery length(Meter) |
Drum Designation |
16 |
7/1.70 |
15.89 |
5.1 |
290 |
44 |
1.789 |
3000 |
PL710 |
25 |
7/7.21 |
24.25 |
6.3 |
425 |
67 |
1.777 |
2500 |
PL1000 |
35 |
7/2.5 |
34.36 |
7.5 |
585 |
94 |
0.831 |
3200 |
PL1000 |
50 |
7/3.0 |
39.48 |
9.0 |
810 |
135 |
0.577 |
2850 |
PL1000 |
50 |
19/1.8 |
48.36 |
9.0 |
860 |
133 |
0.596 |
2850 |
PL1000 |
70 |
19/2.1 |
65.82 |
10.5 |
1150 |
181 |
0.438 |
2500 |
PL1120 |
95 |
19/2.5 |
93.27 |
12.5 |
1595 |
256 |
0.309 |
2500 |
PL1250 |
120 |
19/2.8 |
117.0 |
14.0 |
1910 |
322 |
0.246 |
2000 |
PL1250 |
150 |
37/2.25 |
147.1 |
15.7 |
2520 |
406 |
0.197 |
1800 |
PL1250 |
185 |
37/2.5 |
181.6 |
17.5 |
3105 |
501 |
0.160 |
2300 |
PL1500 |
240 |
61/2.5 |
242.5 |
20.2 |
4015 |
670 |
0.120 |
2300 |
PL1600 |
300 |
61/2.5 |
299.4 |
22.5 |
4850 |
827 |
0.0969 |
2000 |
PL1600 |
400 |
61/2.89 |
400.1 |
26.0 |
6190 |
1105 |
0.0730 |
2400 |
PL1800 |
500 |
61/3.23 |
499.8 |
29.1 |
7600 |
1381 |
0.0580 |
2000 |
PL1800 | |
|
- 铝绞线全标准 - AAC Conductor |
●AAC Conductor All Aluminum Stranded Conductor Standard:GB 1179 |
Nominal cross section(mm2) |
Nos.of Stranding & Diameter(Nos./mm) |
Calculated Cross section area(mm2) |
Approx Overall Diameter(mm) |
Calculated D.C.Resistance at 20℃(Ohm/Km) |
Calculated min.Breaking Load(KN) |
Mass of Conductor(Kg/Km) |
Delivery length(Meter) |
Drum Designation |
16 |
7/1.70 |
15.89 |
5.10 |
1.802 |
290 |
43.5 |
3000 |
PL710 |
25 |
7/2.15 |
25.41 |
6.45 |
1.127 |
444 |
69.6 |
5200×2 |
PL1000 |
35 |
7/2.50 |
34.36 |
7.50 |
0.8332 |
598 |
94.1 |
3200 |
PL1000 |
50 |
7/3.00 |
49.48 |
9.00 |
0.5786 |
809 |
135.5 |
2850 |
PL1000 |
70 |
7/3.60 |
71.25 |
10.80 |
0.4018 |
1117 |
195.1 |
2500 |
PL1120 |
95 |
7/4.16 |
95.14 |
12.48 |
0.3009 |
1474 |
260.5 |
2500 |
PL1250 |
120 |
19/2.85 |
121.21 |
14.25 |
0.2373 |
1982 |
333.5 |
2000 |
PL1250 |
150 |
19/3.15 |
148.07 |
15.75 |
0.1943 |
2379 |
407.4 |
1800 |
PL1250 |
185 |
19/3.50 |
182.80 |
17.50 |
0.1574 |
2902 |
503.0 |
2300 |
PL1500 |
210 |
19/3.75 |
209.85 |
18.57 |
0.1371 |
3292 |
577.4 |
2900 |
PL1600 |
240 |
19/4.00 |
238.76 |
20.00 |
0.1205 |
3700 |
656.9 |
2300 |
PL1600 |
300 |
37/3.20 |
297.57 |
22.40 |
0.09689 |
4781 |
820.4 |
2000 |
PL1600 |
400 |
37/3.70 |
397.83 |
25.90 |
0.074 |
6240 |
1097 |
2400 |
PL1800 |
500 |
37/4.16 |
502.90 |
29.12 |
0.05733 |
7793 |
1387 |
2000 |
PL1800 |
630 |
61/3.63 |
631.30 |
32.67 |
0.04577 |
9382 |
1744 |
1600 |
PL2000 |
800 |
61/4.10 |
805.36 |
36.90 |
0.03588 |
11826 |
2225 |
1150 |
PL2240 | |
●AAC Conductor All Aluminum Stranded Conductor Standard:ASTM B 231-72 |
Code Name |
Conductor Size CM(AWG) |
Stranding(Nos./mm) |
Overall Diameter(mm) |
Calculated Cross Section Area(mm2) |
Mass of Conductor(Kg/Km) |
D.C.Resistance at 20℃(Ohm/Km) |
Rated Strength(Kg) |
Normal Supplying Length(Meter) |
Reel Designation |
Class of Conductor |
AA |
A |
Jessamine |
1750000 |
61/4.303 |
38.73 |
886.9 |
2446 |
0.03239 |
13500 |
1100 |
PL2240 |
O |
- |
Coreopsis |
1590000 |
61/4.100 |
36.90 |
805.2 |
2221 |
0.03568 |
12200 |
1150 |
PL2240 |
O |
- |
Gladiolus |
1510500 |
61/3.998 |
35.98 |
765.6 |
2111 |
0.03752 |
11600 |
1350 |
PL2240 |
O |
O |
Carnation |
1431000 |
61/3.891 |
35.02 |
725.3 |
2000 |
0.03961 |
11000 |
1400 |
PL2240 |
O |
O |
Columbine |
1315000 |
61/3.780 |
34.02 |
684.4 |
1887 |
0.04197 |
10600 |
1550 |
PL2000 |
O |
O |
Narcissus |
1272000 |
61/3.668 |
33.01 |
664.8 |
1777 |
0.04458 |
9990 |
1600 |
PL2000 |
O |
O |
Hawthorn |
1192500 |
61/3.551 |
31.96 |
604.1 |
1665 |
0.04757 |
9550 |
1800 |
PL2000 |
O |
O |
Marigold |
1113000 |
61/3.432 |
30.89 |
564.3 |
1556 |
0.05092 |
8950 |
1760 |
PL1800 |
O |
O |
Bluebell |
1033500 |
37/4.244 |
29.71 |
523.6 |
1443 |
0.05489 |
8050 |
1780 |
PL1800 |
O |
- |
Larkspur |
1033500 |
61/3.307 |
29.76 |
523.9 |
1445 |
0.05485 |
8290 |
1780 |
PL1800 |
- |
O |
Hawkweed |
1000000 |
37/4.176 |
29.23 |
506.9 |
1397 |
0.05671 |
7780 |
1780 |
PL1800 |
O |
- |
Camellia |
1000000 |
61/3.251 |
29.26 |
506.4 |
1396 |
0.05675 |
8020 |
1780 |
PL1800 |
- |
O |
Magnolia |
945000 |
37/4.079 |
28.55 |
483.6 |
1333 |
0.05944 |
7410 |
2000 |
PL1800 |
O |
- |
Goldenrod |
954000 |
61/3.178 |
28.60 |
483.9 |
1334 |
0.05939 |
7630 |
2000 |
PL1800 |
- |
O |
Cockscomb |
900000 |
37/3.962 |
27.73 |
465.2 |
1257 |
0.06299 |
7000 |
2100 |
PL1800 |
O |
- | |